Product Overview
The XGN15-12 type unit-type AC metal-enclosed ring network switchgear (hereinafter referred to as ring network switchgear), also professionally defined as ring main unit switchgear, is a high-performance hv ring main unit and innovative gis rmu newly developed by our company. Designed by absorbing advanced foreign technologies, it fully satisfies the application demands of domestic rural power grids and urban power network reconstruction projects. The XGN15 12 type switchgear supports both manual and electric operation modes, and all its technical performance indicators fully comply with IEC62271-200:2003 and GB3906 standards.
This 11 kV ring main unit, as a reliable hv ring main unit and compact gis rmu, is ideal for receiving and distributing electric energy in AC 50Hz, 12kV power networks. The cabinet is assembled by riveting after CNC machining, ensuring a protection grade of IP3X. The XGN15-12 ring main unit switchgear is equipped with reliable mechanical interlocking and anti-misoperation devices to guarantee operational safety. In addition, the main switch inside the cabinet adopts an SF6 switch, delivering long service life and stable operational reliability.
Type and meaning

Main Technical Parameters of Vacuum Circuit Breaker
|
No. |
Name |
Unit |
Value |
|
1 |
Rated voltage |
kV |
12 |
|
2 |
Rated frequency |
Hz |
50 |
|
3 |
Rated current of main busbar/maximum rated current off use |
A |
630,125 |
|
4 |
Rated short-time withstand current of main circuit and ground circuit |
kA/s |
20/3 |
|
5 |
Rated peak withstand current of main circuit and ground circuit |
kA |
50 |
|
6 |
Rated short-circuit closing current of main circuit and ground circuit |
kA |
50 |
|
7 |
Breaking times of load switch at full capacity |
times |
100 |
|
8 |
Breaking current of fuse |
kA |
31.5,40 |
|
9 |
Rated breaking current of closed-loop |
A |
630 |
|
10 |
Rated transfer current |
A |
1600 |
|
11 |
Mechanical life |
times |
2000 |
|
12 |
1min power frequency withstand voltage(peak value) phase-to-phase, to ground/isolation fracture |
kV |
42,48 |
|
13 |
Lightning impulse with stand voltage(peak value) phase-to-phase, to ground/isolation fracture |
kV |
75,85 |
|
14 |
Secondary circuit 1min power frequency withstand voltage |
kV |
2 |
|
15 |
Protection level |
IP3X |


Hot Tags: Gas-Insulated, Fixed-Type, 12 kV, Sealed Ring Main Unit (RMU) Switchgear, China Gas-Insulated, Fixed-Type, 12 kV, Sealed Ring Main Unit (RMU) Switchgear manufacturers, suppliers, factory, 33 kv gis, 33 kv gas insulated switchgear, 33kv gis switchgear, high voltage gas insulated switchgear, 33kv gas insulated switchgear, gis switchgear