Fixed-Type, 12 kV, Sealed Ring Main Unit (RMU) - HXGN17-12 Series

Fixed-Type, 12 kV, Sealed Ring Main Unit (RMU) - HXGN17-12 Series

HXGN17-12 box-type fixed AC metal-enclosed switchgear (referred to as ring network cabinet) is a complete set of AC high-voltage electrical equipment with a rated voltage of 12kV and a rated frequency of 50Hz. It is mainly used for receiving and distributing electric energy in three-phase AC ring network, terminal power distribution, power grid and industrial power equipment. It is also suitable for the installation into box-type substations.

Product Overview

 

The HXGN17-12 box-type fixed AC medium voltage metal-enclosed switchgear (referred to as the ring network cabinet) is a complete set of AC high-voltage electrical equipment with a rated voltage of 12kV and a rated frequency of 50Hz, and also serves as a high-performance 11 kv switchboard perfectly matching 11kV power distribution systems. This medium voltage metal-enclosed switchgear and dedicated 11 kv switchboard is mainly used for receiving and distributing electric energy in three-phase AC ring network systems, terminal power distribution, power grids, and industrial power equipment. It is also suitable for installation in switchgear cabinets within box-type substations as a compact and stable 11 kv switchboard.

 

For higher capacity applications, the 33kV switchgear can be integrated into the system, providing enhanced performance and reliability in handling higher voltage levels. The HXGN17-12 ring network cabinet, as a core 11 kv switchboard and essential medium voltage metal-enclosed switchgear, is a key component in modern power distribution, ensuring safe and efficient energy management within medium voltage metal-enclosed switchgear installations.

 

Type and meaning

 

 

301

Working Conditions

 

 

  • Ambient air temperature: -25℃ ~+40℃;
  • Humidity conditions:
  • Daily average value is not more than 95%, and the daily average value of water vapor pressure is not more than 2.2kPa;
  • Monthly average value is not more than 90%, and the monthly average value of water vapor pressure is not more than 1.8kPa;
  • Seismic intensity: no more than 8 degrees;
  • Places without obvious pollution such as corrosive or flammable gases;

Note: When the above normal use conditions are exceeded, the user can negotiate with our company.

 

Main Technical Parameters of Vacuum Circuit Breaker

 

 

No.

Name

Unit

FN12-10

FZN25-12

1

Rated voltage

kV

12

2

1min power frequency with stand voltage

kV

To ground and between phases 42, Isolation fracture 48

3

Lightning impulse voltage(peak value)

kV

To ground and between phases 75, Isolation fracture 85

4

Rated frequency

Hz

50

5

Rated current of main busbar

A

630

6

LOAD SWITCH

Rated current

A

630

7

Electrical life at rated current

times

No less than 100

8

Breaking capacity of no-load transformer

kVA

1250

9

Rated thermal stability current

kA

20/4; Earthing switch 20/2

10

Rated dynamic stability current(peak value)

kA

50

11

Rated short-circuit making current(peak value)

kA/s

50

 

302001
303001

 

Hot Tags: Fixed-Type, 12 kV, Sealed Ring Main Unit (RMU) - HXGN17-12 Series, China Fixed-Type, 12 kV, Sealed Ring Main Unit (RMU) - HXGN17-12 Series manufacturers, suppliers, factory, 10 kv switchgear, 11 kv switchboard, hv ring main unit, indoor type switchgear, outdoor cable distribution box, outdoor ring main unit