ZN63A(VS1)-12 Indoor High Voltage Vacuum Circuit Breaker (Handcart Type, Solid-sealed Pole)
video
ZN63A(VS1)-12 Indoor High Voltage Vacuum Circuit Breaker (Handcart Type, Solid-sealed Pole)

ZN63A(VS1)-12 Indoor High Voltage Vacuum Circuit Breaker (Handcart Type, Solid-sealed Pole)

ZN63A(VS1)-12 series indoor fixed high voltage vacuum circuit breaker is a indoor switch equipment with three-phase AC 50Hz and rated voltage of 12 kV. It can be used for the control and protection in industrial and mining enterprises, power plants, substations and electrical facilities, and is also suitable for place where needs frequent operation.

Product Overview

 

The ZN63A(VS1)-12 series vacuum circuit breaker indoor is a high-voltage switch device with three-phase AC 50 Hz and a rated voltage of 12 kV. This vacuum circuit breaker indoor equipment can be used for control and protection in industrial and mining enterprises, power plants, substations, and electrical facilities, and is especially suitable for places requiring frequent operation.

As a reliable indoor vacuum circuit breaker, it meets the standards of GB1984-2014 AC High Voltage Circuit Breakers, JB3855-1996 3.6–40.5 kV Indoor AC High Voltage Vacuum Circuit Breakers, DL403-91 10–35 kV Indoor AC High Voltage Circuit Breakers Order Technical Conditions, and the relevant requirements of IEC56 (87 Publications). The product integrates the operating mechanism with the circuit breaker body. It can be used as a fixed installation unit or equipped with a special propelling mechanism to serve as a handcart unit, ensuring the vacuum circuit breaker indoor remains versatile and dependable for modern power systems.

 

Type and meaning

 

 

165

 

Usage Environment

 

 

1. Environmental temperature: not higher than 40℃, not lower than -10℃ (storage and transportation at -30℃ is allowed).

2. Altitude: no more than 1 000m. (If the altitude is increased, the rated insulation level will be increased accordingly.)

3. Relative humidity: daily mean value is not more than 95%. The average daily value of saturated vapor pressure is not more than 2.2×10⁻³MPa, and the monthly mean value is not more than 1.8× 10⁻³MPa.

4. Seismic intensity: no more than 8 degrees.

5. Places without fire, explosion, serious pollution, chemical corrosion and violent vibration.

 

Produce Construction and Features

 

 

1.Vacuum interrupter
The circuit breaker is equipped with intermediate sealing type ceramic or glass vacuum interrupter, using copper contact material, and cup-shaped longitudinal magnetic field contact structure. The contact has small electrical wear rate, long electrical life, high voltage resistance of contact, stable dielectric insulation strength, fast recovery after arc, low cut-off level and strong breaking ability.

 

2.Overall structure
The overall structure of the circuit breaker adopts an arrangement where the operating mechanism is positioned at the front and the interrupter at the rear. The main circuit is divided into three phases of the floor structure, and the vacuum arc extinguishing chamber is longitudinally installed in a tubular insulation cylinder, which is made of epoxy resin and poured by APG process, so it is particularly resistant to creepage. This structure design greatly reduces the accumulation of dust on the surface of the interrupter, which can not only prevent the vacuum interrupter from being damaged by external factors, but also ensure that the voltage effect can show a high positive state even in hot and humid and badly polluted environment.
The main circuit current path when the circuit breaker is in the closing position.
Upper outlet seat 28 through the upper support fixed on the interrupter 7 to the static contact in the vacuum interrupter, through the moving contact and the connected conductive clip, soft connection, to the lower support 30, the lower outlet seat 32. The insulated pull rod 34 and the internal over-range spring 33 pass through the circuit breaker connecting rod system to complete the operating movement of the circuit breaker and the contact of the protective contacts.
The circuit breaker is equipped with a dust-proof insulated cylinder cover for each current level before delivery. In actual use, with the rated current 1250A and below the product can be operated without removal, but the rated current 1600A and above, the cover must be removed.

 

3. Operating mechanism
The operating mechanism is the plane layout of spring energy storage type operating mechanism, with manual energy storage and electric energy storage function. The operating mechanism is positioned in a mechanism box located in front of the interrupter, and the circuit mechanism can also serves as the the operating mechanism frame. The mechanism box is divided into five assembly spaces by four intermediate partitions, which are respectively equipped with the energy storage part, the transmission part, the tripping part and the buffer part of the operating mechanism. The front part of box includes closing and opening buttons, manual energy storage operation holes, spring energy storage state indicator, and closing and opening indicator. In this way, the interrupter and the mechanism are arranged before and after to form a whole, so that the two are more consistent, reduce unnecessary intermediate transmission links, reduce energy consumption and noise, and make the performance of the circuit breaker more reliable.

 

4. The circuit breaker has the advantages of long life, simple maintenance, no pollution, no explosion risk, low noise, and is suitable for frequent operation and other harsh working conditions. The circuit breaker can be installed in either a handcart type switchgear or a fixed type switchgear.

 

Main technical parameters

 

 

No.

Item

Unit

Parameter

1

Rated voltage

kV

12

2

Rated current

A

630
1250

630 1250
1600 2000
2500 3150

1250 1600
2000 2500
3150 4000

3

Rated short circuit breaking current

KA

20/25

31.5

40

4

Rated short circuit closing current (peak value)

KA

50/63

80

100

5

Rated thermal stable current (effective value)

kA

20/25

31.5

40

6

Rated dynamic stable current (peak value)

KA

63

80

100

7

Rated insulation
level

1min power frequency withstand voltage

kV

42

Rated lightning impulse withstand voltage peak

kV

75

8

Rated thermal stability time

S

4

9

Rated operation ranking

 

O-0.3S-CO-180S-CO / O-0.3S-CO-180S-CO(40kA)

10

Power-frequency withstand current of secondary circuit (1 min)

V

20000

11

Breaking times of rated short circuit breaking current

Times

80

50

30

12

Rated single/back-to-back capacitor bank breaking current

A

630/400

800/400

13

Mechanical life

Times

20000

10000

14

Contact distance

mm

11±1

15

Contact travel

mm

3.3±0.6

16

Average closing speed(6mm~contact closure)

m/s

0.6±0.2

17

Average opening speed

m/s

1.1±0.2

18

Opening time(rated voltage)

m/s

20~50

19

Closing time(rated voltage)

m/s

35~70

20

Close-bounce time of contact

ms

≤2

≤3(40kA)

21

Different periods of three-phase switching

≤2

22

Leading circuit resistance

μΩ

<50(630A) <45(1250A)
<35(1600~2000A) <25(2500A above)

23

Permissible wear cumulative thickness of moving and static contact

mm

2000±200(20kA) 2400+200(25kA)
3100+200(31.5kÁ) 4500+250(40KA

 

Working Principle

 

 

1. Energy storage action
The energy required to close the circuit breaker is provided by the energy storage of the closing spring, which can be completed either by driving the motor with an external power supply or manually by using the energy storage handle.
Energy storage operation: The energy storage motor 15 fixed on the frame is powered to output torque code, and the sprocket 14 is driven to rotate through the single bearing 13 of the motor output shaft 16, or the energy storage handle is inserted into the manual energy storage hole and rotated clockwise, and the sprocket 14 is driven to rotate through the worm wheel (11, 10), and then the sprocket 3 is driven to rotate through the chain 9. When the sprocket 3 rotates, the gear pin 1 pushes the slider 2 on the wheel 5 to make the energy storage shaft 21 follow the rotation, and the energy storage is carried out by stretching the closing spring through the crank arms 19 on both sides. When the energy storage position is reached, the limit pole on the frame will press down slider 2 to disconnect the energy storage shaft from the sprocket wheel drive system, and the energy storage holding button 7 will resist the roller 6 to keep the energy storage position. Meanwhile, the dial plate 23 on the energy storage shaft will drive the energy storage indicator to flip, showing the energy storage mark, and switch the stroke switch to cut off the power supply of the energy storage motor. At this time, the circuit breaker is in the closing state.

 

2. Closing operation
After the energy storage of the mechanism, the closing signal is received, the closing electromagnet 17 acts or presses the closing button, so that the energy storage holding shaft rotates, driving the button 7 to release the roller 6 and disengaging the energy storage holding. The closing spring 18 releases energy, so that the energy storage shaft 21 and the CAM 22 on the shaft rotate clockwise, and the driving plate 37 drives the insulating pull rod 34 to drive the moving contact up into the closing position through the transmission arms 36, and compresses the super range spring 33 to maintain the pressure required by the contact.
After the closing action is completed, the closing hold button 40 and half shaft 42 shall maintain the closing position; meanwhile, the energy storage indicator and the energy storage stroke switch shall be reset; the power supply circuit of the motor shall be connected; the closing indicator shall show the "ON" mark; if the external power supply is also connected, the energy storage state shall be entered again.
Note: When the circuit breaker is in the closing state or the latching device is selected, but the external power supply is not connected or the handcart circuit breaker is in the process of pushing, the closing operation cannot be carried out.

 

3. Opening operation
After the closing operation is completed, once the opening signal is received or the opening button is pressed, the opening exit electromagnet or the over-current tripping electromagnet will act, so that the constraint of the opening half shaft 42 on the closing hold button 40 will be released. By the ability of storage of the super range spring 33 and the brake spring 35, the moving and static contacts of the interrupter 29 are disconnected to realize the opening operation. In the latter part of the opening process, the hydraulic buffer absorbs the residual energy of the opening process and limits the opening position. The indicator shows the mark of "OFF". At the same time, the counter 43 is pulled to realize the counting of the counter. The main and auxiliary switches are switched by the driving connecting rod.

 

Maintenance

 

 

1. During the normal use of the circuit breaker, the body of the circuit breaker should be properly inspected regularly. Clean the dirt and moisture on the surface of the equipment, wipe the insulating surface with a dry cloth, and then wipe off other dirt with a silk cloth stained with detergent (note that the detergent can be applied to plastic or synthetic plastic materials). The vacuum degree of the vacuum interrupter is checked by the power frequency voltage withstand method. It is normal to have weak lighting outside the interrupter during the voltage withstand process. If continuous breakdown of the interrupter is found, the interrupter should be replaced.

2. When the circuit breaker is placed for a long time, the active part of the circuit breaker may be blocked. The energy storage and closing and opening operation of the circuit breaker should be carried out at least 5 times a year.

3. It is strictly forbidden to hit the vacuum interrupter with hard objects during installation and use.

4. The user should not arbitrarily replace the use of electrical components inconsistent with the original model specifications.

5. The operator should have a preliminary understanding of the structure, performance, installation, debugging and maintenance of the circuit breaker and the mechanism, record the operation problems, and notify the manufacturer if necessary.

6. Frequent operation places should be strictly controlled within the range of operation times and switching times specified in technical conditions, and should not continue to use beyond the service life.

 

Overall and installation dimension

 

169

1691

Hot Tags: zn63a(vs1)-12 indoor high voltage vacuum circuit breaker (handcart type, solid-sealed pole), China zn63a(vs1)-12 indoor high voltage vacuum circuit breaker (handcart type, solid-sealed pole) manufacturers, suppliers, factory