FKN12-12D/T630-20FKN12-12RD/T200-31.5 Indoor High Voltage Pneumatic Load Switch
video
FKN12-12D/T630-20FKN12-12RD/T200-31.5 Indoor High Voltage Pneumatic Load Switch

FKN12-12D/T630-20FKN12-12RD/T200-31.5 Indoor High Voltage Pneumatic Load Switch

FKN12-12D/630-20 indoor AC high-voltage load switch (hereinafter referred to as FKN-12D load switch) is a three-phase high-voltage on-off with a rated voltage of 12KV and a fixed frequency of 50 Hz equipment for split-load current, closed-loop current, no-load transformer and cable charging current, Close the short circuit current.

Product Overview

 

The FKN12-12D/630-20 indoor high-voltage isolating switch (hereinafter referred to as the FKN-12D load switch) is a three-phase high-voltage device with a rated voltage of 12 kV and a frequency of 50 Hz, used for splitting load current, closed-loop current, no-load transformer and cable charging current, and for closing short-circuit current. This indoor high-voltage isolating switch can be equipped with a grounding switch to withstand short-circuit conditions.

The FKN12-12R.D/125-31.5 indoor high-voltage isolating switch-fuse combination (FKN-12R.D) integrates the FKN-12D load switch with S□LAJ-12(XRNT□-12) high-pressure current-limiting fuses, providing reliable interruption of any current up to the short-circuit level. This design ensures safe operation and effective protection across a wide range of overcurrent scenarios.

 

Model Meaning

 

 

15

16

 

Main Technical Parameters

 

 

No.

Item

Unit

FKN12-12D/630-20

FKN12-12R.D/125-31.5

1

Rated Voltage

kV

12

2

Rated Frequency

Hz

50

3

Rated Current

A

630

125

4

Lightning Impulse Withstand Voltage

kV

Ground and Phase-to-Phase, Isolation Break: 85

5

1-minute Power Frequency Withstand Voltage

kV

Ground Phase-to-Phase: 42, Isolation Break: 48

6

Rated Thermal Withstand Current

kA

20(4S)

7

Rated Dynamic Withstand Current

kA

50

8

Rated Making Current (Peak)

kA

50

-

9

Rated Short-circuit Breaking Current

kA

-

31.5

10

Rated Transfer Current

kA

-

1.5

11

Maximum Breaking Current (Reference Value)

kA

1.8

12

No-load Transformer Capacity Breaking

kVA

1250

13

Rated Cable Charging Current

A

10

14

Rated Active Load Current Breaking Times

times

>100

15

Actuator Triggered Load Switch Opening Time

S

-

> 0.06

16

Earthing Switch Thermal Withstand Current

kA

20(2S)

20(2S)

17

Earthing Switch Thermal Withstand Current (Peak)

kA

50

50

18

Motor Operating Power Supply Voltage

V

AC220, DC48

 

Working Condition

 

 

  • Ambient air temperature: upper limit +40°C, lower limit -25°C;
  • Altitude: 1000m and below;
  • Relative humidity: monthly average not exceeding 90%,
  • Daily average not exceeding 95%;
  • The surrounding air should not be significantly contaminated by corrosive or flammable gases and water vapor, etc.: no frequent violent movement;
  • Pollution resistance level: Class II.
  • If the usage conditions exceed the above specifications, they shall be determined through consultation between the user and the manufacturer.

 

Outline and mounting dimensions

 

 

22

 

17001
19001
21001

 

Hot Tags: fkn12-12d/t630-20fkn12-12rd/t200-31.5 indoor high voltage pneumatic load switch, China fkn12-12d/t630-20fkn12-12rd/t200-31.5 indoor high voltage pneumatic load switch manufacturers, suppliers, factory