FZN66-12D/T630-25 Three-Position Vacuum Load Break Switch

FZN66-12D/T630-25 Three-Position Vacuum Load Break Switch

The FZN66 series load switches and their combined electrical apparatus are developed by our factory through the digestion and absorption of advanced foreign technology, combined with improvements based on the requirements of domestic users.

Product Overview

 

The FZN66 series hv switch load devices and their combined electrical apparatus are advanced high-voltage products developed using absorbed foreign technology and improved for domestic needs. These hv switch units meet the standards GB/T3804 "3~6kV AC High-Voltage Load Switches" and GB/T16926 "AC High-Voltage Load Switch-Fuse Combination Electrical Apparatus." Designed for 3.6–12 kV, 50 Hz three-phase systems, the hv switch provides reliable power distribution. Each unit also functions as a load switch circuit, offering efficient energy reception and distribution for ring main units, box-type substations, and various power distribution equipment.

 

Model Meaning

 

 

54

Main Technical Parameters

 

 

No.

Item

Unit

Vacuum Load Switch

Vacuum Load Switch-Fuse Combination Appliance
FZRN64-12(D)/T200-31.5

FZN66-12(D)/T630-25

FZN66-12(D)/T1250-25

1

Rated Voltage

kV

12

2

Rated Frequency

Hz

50

3

Rated Current

A

630

1250

200

4

Rated Short-time Withstand Current

kA

25

5

Rated Peak Withstand Current

kA

63

6

Rated Short-circuit Making Current

kA

63

80

7

Rated Active Load Breaking Current

A

1250

1250

8

Rated Loop-breaking Current

A

1250

1250

6

No-load Transformer Breaking

kVA

2000
20

10

Earth Fault Current

A

20

11

Line and Cable Charging Current under Earth Fault Conditions

A

20

12

Rated Short-circuit Breaking Current

kA

31.5/50(Determined by the fuse)

13

Rated Transfer Current

A

3150

14

Fixed Breaking Time

ms

45

15

Power Frequency Withstand Voltage, 1min

kV

Phase-to-Phase, Phase-to-Ground, Vacuum Break: 42; Isolation Break: 48

16

Lightning Impulse Withstand Voltage

kV

Phase-to-Phase, Phase-to-Ground, Vacuum Break: 75; Isolation Break: 85

17

Mechanical Life

times

>10000

 

Working Condition

 

 

  • Ambient Air Temperature: Upper limit +40°C; Lower limit -25°C (storage and transportation allowed at -30°C).
  • Altitude: 1000m.
  • Relative Humidity: Daily average not exceeding 95%; Monthly average not exceeding 90%.
  • Seismic Intensity: Not exceeding 8 degrees.
  • The surrounding air should not be significantly polluted by corrosive or flammable gases, water vapor, etc.
  • Locations without frequent severe vibration.
  • Pollution Level: Class II.

 