Product Overview
The FZN66 series hv switch load devices and their combined electrical apparatus are advanced high-voltage products developed using absorbed foreign technology and improved for domestic needs. These hv switch units meet the standards GB/T3804 "3~6kV AC High-Voltage Load Switches" and GB/T16926 "AC High-Voltage Load Switch-Fuse Combination Electrical Apparatus." Designed for 3.6–12 kV, 50 Hz three-phase systems, the hv switch provides reliable power distribution. Each unit also functions as a load switch circuit, offering efficient energy reception and distribution for ring main units, box-type substations, and various power distribution equipment.
Model Meaning

Main Technical Parameters
|
No. |
Item |
Unit |
Vacuum Load Switch |
Vacuum Load Switch-Fuse Combination Appliance |
|
|
FZN66-12(D)/T630-25 |
FZN66-12(D)/T1250-25 |
||||
|
1 |
Rated Voltage |
kV |
12 |
||
|
2 |
Rated Frequency |
Hz |
50 |
||
|
3 |
Rated Current |
A |
630 |
1250 |
200 |
|
4 |
Rated Short-time Withstand Current |
kA |
25 |
||
|
5 |
Rated Peak Withstand Current |
kA |
63 |
||
|
6 |
Rated Short-circuit Making Current |
kA |
63 |
80 |
|
|
7 |
Rated Active Load Breaking Current |
A |
1250 |
1250 |
|
|
8 |
Rated Loop-breaking Current |
A |
1250 |
1250 |
|
|
6 |
No-load Transformer Breaking |
kVA |
2000 |
||
|
10 |
Earth Fault Current |
A |
20 |
||
|
11 |
Line and Cable Charging Current under Earth Fault Conditions |
A |
20 |
||
|
12 |
Rated Short-circuit Breaking Current |
kA |
31.5/50(Determined by the fuse) |
||
|
13 |
Rated Transfer Current |
A |
3150 |
||
|
14 |
Fixed Breaking Time |
ms |
45 |
||
|
15 |
Power Frequency Withstand Voltage, 1min |
kV |
Phase-to-Phase, Phase-to-Ground, Vacuum Break: 42; Isolation Break: 48 |
||
|
16 |
Lightning Impulse Withstand Voltage |
kV |
Phase-to-Phase, Phase-to-Ground, Vacuum Break: 75; Isolation Break: 85 |
||
|
17 |
Mechanical Life |
times |
>10000 |
||
Working Condition
- Ambient Air Temperature: Upper limit +40°C; Lower limit -25°C (storage and transportation allowed at -30°C).
- Altitude: 1000m.
- Relative Humidity: Daily average not exceeding 95%; Monthly average not exceeding 90%.
- Seismic Intensity: Not exceeding 8 degrees.
- The surrounding air should not be significantly polluted by corrosive or flammable gases, water vapor, etc.
- Locations without frequent severe vibration.
- Pollution Level: Class II.
Hot Tags: fzn66-12d/t630-25 three-position vacuum load break switch, China fzn66-12d/t630-25 three-position vacuum load break switch manufacturers, suppliers, factory