FZN25A-12D/T630-20 FZRN25A-12D/T200-31.5 Indoor AC High-Voltage Vacuum Load Switch-Fuse Combination Appliance
video
FZN25A-12D/T630-20 FZRN25A-12D/T200-31.5 Indoor AC High-Voltage Vacuum Load Switch-Fuse Combination Appliance

FZN25A-12D/T630-20 FZRN25A-12D/T200-31.5 Indoor AC High-Voltage Vacuum Load Switch-Fuse Combination Appliance

The FZN25A-12D/T630-20 indoor AC high-voltage vacuum load switch is a three-phase, 50Hz, rated voltage 12KV indoor device, suitable for use in power distribution stations and substations of industrial and mining enterprises. It serves as protection and control for electrical facilities, used for switching load current, loop current, no-load transformers, and cable charging current.It is equipped with an earthing switch capable of closing short-circuit current.

Product Overview

 

The FZN25A-12D/T630-20 indoor AC high-voltage vacuum electrical load switch is a three-phase, 50 Hz, 12 kV indoor device used in power distribution stations and substations of industrial and mining enterprises. This electrical load switch provides protection and control for electrical facilities, handling switching of load current, loop current, no-load transformers, and cable charging current. It also features an earthing switch capable of closing short-circuit current, ensuring safe operation even under load on switch conditions.

The FZRN25A-12D/T200-31.5 indoor AC high-voltage vacuum power load switch and fuse combination apparatus offers similar functions, including short-circuit protection and reliable load control. With manual or motorized operation, this electrical load switch supports remote signaling, remote measurement, and remote control, making it ideal for modern power system requirements.

 

Model Meaning

 

 

52

53

 

Main Technical Parameters

 

 

No.

Item

Unit

Parameter

FZN25A-12D/T630-20

FZRN25A-12D/T200-31.5

1

Rated Voltage

kV

12

2

Rated Current

A

630

200

3

Rated Frequency

HZ

50

4

Rated Insulation Level

1-minute Power Frequency Withstand Voltage

kV

Arc Extinguishing Chamber Break: 30;Ground and Phase-to-Phase: 42;Isolation Break: 48

Lightning Impulse Withstand Voltage (Peak)

kV

Ground and Phase-to-Phase: 75;Isolation Break: 85

5

Rated Short-time Withstand Current

kA

20

 

6

Rated Short-circuit Duration

S

4

 

7

Rated Peak Withstand Current

kA

50

 

8

Rated Active Load Breaking Current

A

630

 

6

Rated Loop-breaking Current

A

630

 

10

Rated Cable Charging Breaking Current

A

10

 

11

Rated No-load Transformer Breaking Capacity

kVA

1600

12

Rated Short-circuit Breaking Current

kA

-

31.5

13

Rated Transfer Current

A

 

2000

14

Fuse Model

   

SDLAJ-12, XPNT1-12

15

Actuator Output Energy

J

 

1+0.5

16

Rated Short-circuit Making Current

kA

 

80(Prospective Peak)

17

Earthing Switch Rated Short-time Withstand Current

kA

20

18

Earthing Switch Rated Short-circuit Duration

S

2

19

Earthing Switch Rated Peak Withstand Current

kA

50

20

Auxiliary Circuit Rated Voltage

V

220V,110

21

Mechanical Life

times

10000

 

Working Condition

 

 

  • Ambient Air Temperature: Upper limit +40°C; Lower limit -25°C (storage and transportation allowed at -30°C).
  • Altitude: 1000m.
  • Relative Humidity: Daily average not exceeding 95%; Monthly average not exceeding 90%.
  • Seismic Intensity: Not exceeding 8 degrees.
  • The surrounding air should not be significantly polluted by corrosive or flammable gases, water vapor, etc.
  • Locations without frequent severe vibration.
  • Pollution Level: Class II.

 